Section 5
Operating the RMBE Series
5.1 Jumper Configuration
5.1.1 Configuration Jumper Settings
Before connecting the RMBE to a system, the configuration jumpers must be set for proper
operation. Do not change jumper settings while output wiring is connected to the system or
damage to the system may occur. The proper number of pluggable configuration jumpers are
provided with all RMBE enclosures. These jumpers are keyed and can only be installed in one
orientation.
Fig 5.1.1
12V24V
Battery Set 2 Configuration
OR
IN-Parallel Set 1 and 2
OUT-Separates Set 1 and 2
BATTERY
CONNECT
+
-
+
-
The RMBE contains 2 battery sets which may be configured for:
12V / 12V - Two separate outputs; 24V / 24V Two separate outputs
12V and 24V - Two separate outputs
12V - One single output or 24V - One single output
VOLTAGE SELECTION
+
-
+
-
- ONLY ONE VOLTAGE SELECTION PLUG
CAN BE INSTALLED TO EACH BAT SET
For complete information, read Installation
Instruction manual 52-342 or internal label.
Battery Set 1 Configuration
OR
5.1.1.1 Voltage Selection Jumpers
For each battery set, only ONE voltage selection jumper must be in place. The back panel of
the RMBE is labelled for the voltage selection options. Each battery set may be configured
individually for 12VDC or 24VDC nominal.
NOTE - When the paralleling jumper is in place (See Section 5.1.1.2) BOTH voltage selection
jumpers MUST be set for the same voltage or damage to the system may occur.
5.1.1.2 Parallel Set 1 and 2 Jumper
When this jumper is in place, the two battery sets are paralleled internally to create one
battery set of double the AH capacity. Care must be taken to ensure both battery sets are
configured for the same voltage before installing this jumper (See Section 5.1.1.1).
5.1.1.3 Configuration Options for the RMBE Battery Enclosure
14AH @ 24V (Single Output)In24V24V
7AH @ 24V7AH @ 24VOut24V24V
14AH @ 12V7AH @ 24VOut12V24V
7AH @ 24V14AH @ 12VOut24V12V
28AH @ 12V (Single Output)In12V12V
14AH @ 12V14AH @ 12VOut12V12V
Output 2Output 1
Parelleling
Jumper
Voltage -
Batt Set 2
Voltage -
Batt Set 1
Rack Mount Battery Enclosure Installation Instructions
5/27/2009, 11:42:41 AM
52-342 Rev A.01
Page 10 of 14