Process Temperature Display (3 Digit)
Setpoint, Percent Output, or Heater
Current Display (4 Digit)
Heat On Indicator (Orange)
Alarm Indicator (Orange)
Up Arrow
Increases temperature setpoint in normal
mode or increases values in menu mode
(Hold for fast-step progression)
Display - Setpoint, Percent Output, or
Heater Current. When held for 3 seconds ,
it displays menu (PID).
Auto / Manual Mode (Green)
(LED On Indicates “Manual”)
Down Arrow
Decreases temperature setpoint in normal
mode or decreases values in menu mode
(Hold for fast-step progression)
Power
(MUST BE OFF TO REMOVE OR
INSTALL UNIT)
8 9
PROPORTIONAL BANDWIDTH
Proportional Band is the amount of deviation of the controlled variable
required to move through the full range (expressed in % of span or degrees
of temperature). It is an expression of Gain (the wider the band, the lower the
gain.) This item is accessible within the Menu. This PID control parameter is
adjustable from 0.1 to 999
o
F/537
o
C.
RATE
Rate is a control function that produces a corrective signal proportional to
the rate at which the controlled variable is changing. Rate action produces a
faster corrective action than proportional action alone. Also referred to as
Derivative action, Rate is useful in eliminating overshoot and undershoot.
This item is accessible within the Menu. This PID control parameter is
adjustable from 0.0 to 999.
RESET
Reset is a control function that produces a corrective signal proportional to
the length of time and magnitude the controlled variable has been away from
the setpoint. Reset action accommodates load changes, and is also known
as Integral action. This item is not accessible within the Menu as the Reset
parameter tracks the Rate parameter by a fixed ratio.
AUTOTUNE
When “At.OP” appears on the display, it will toggle with one of the following.
Press the UP/DOWN keys to change setting.
EnA ENABLE: Tunes every time power is applied.
oncE ONCE: Tunes the first time power is applied, then reverts
to disable.
dlS DISABLE: Uses currently stored PID values.
The PID menu contains three items. Enter the menu by holding down the
DISPLAY KEY for three seconds and pressing the MODE KEY to index
through the parameters. Exit the menu by holding down the DISPLAY KEY
for three seconds.
Pb Proportional Band
rAte Derivative w/tracking integral
At.OP Autotune Operation (enable/once/disable)
! To adjust parameters use the up or down keys.
! To select next item in menu use the MODE key.
Entering and Changing
Parameter Values
Parameter
Descriptions